Que posibles averías pueden dar el error U1?
Aire Acondicionado Mitsubishi Electric
Servicio Técnico Oficial Valencia
Necessary cookies are absolutely essential for the website to function properly. This category only includes cookies that ensures basic functionalities and security features of the website. These cookies do not store any personal information.
Any cookies that may not be particularly necessary for the website to function and is used specifically to collect user personal data via analytics, ads, other embedded contents are termed as non-necessary cookies. It is mandatory to procure user consent prior to running these cookies on your website.
Buenas noches,
El error U1 está indicando un error en el presostato de gas de la unidad, por falta o exceso de gas, si la avería la provoca el presostato de alta lo normal es que tengas la unidad exterior muy sucia o no funcione el ventilador exterior, ya sea por fallo en el ventilador o la placa que lo controla.
Si el error lo provoca el presostato de baja presión, puedes tener una falta de refrigerante (fuga de gas), que los filtros de la unidad interior estén muy muy sucios o no funcione el ventilador interior.
En ambos casos, por alta o baja presión, puedes tener también un fallo en el propio presostato, en el cable que va desde este hasta la placa electrónica de control exterior o un fallo en la propia placa, que aun estando todo correcto de dicho error.